65 model controller supports continuous measurement of signal coming from one or two sensors.
Thanks to modular structure, signal input boards can be replaced in field conditions that simplifies configuration changes.
High resolution color screen has excellent quality and functional capabilities in comparison with displays of other analytical devices.
High resolution color screen offers a convenient view of measurement results and dynamic diagrams, including diagnostics.
Real-time user help – detailed instructions and pieces of advice for troubleshooting in several languages.
Data logger and event logger – uploading of activity data and information about emergency conditions stamped with date and time through USB 2.0.
Control – possibility of PID regulation and proportionate regulation by time. Availability of synchronized interval timers and four special applied functions.
In-built preamplifier with SMART technology for electrochemical analog sensors.
65 model controller supports continuous measurement of signal coming from one or two sensors.
Thanks to modular structure, signal input boards can be replaced in field conditions that simplifies configuration changes.
High resolution color screen has excellent quality and functional capabilities in comparison with displays of other analytical devices.
High resolution color screen offers a convenient view of measurement results and dynamic diagrams, including diagnostics.
Real-time user help – detailed instructions and pieces of advice for troubleshooting in several languages.
Data logger and event logger – uploading of activity data and information about emergency conditions stamped with date and time through USB 2.0.
Control – possibility of PID regulation and proportionate regulation by time. Availability of synchronized interval timers and four special applied functions.
In-built preamplifier with SMART technology for electrochemical analog sensors.
Technological information and specifications |
|||
Casing material |
Polycarbonate. NEMA 4X/CSA 4 |
||
Dust and moisture protection |
IP65 |
||
Cable conduit openings |
It is possible to use ½ inch fitting or PG13.5. |
||
Display |
High-resolution large color LCD 95.3 x 55.9 mm (3.75 x 2.2 in.) reflects the main process parameters and diagnostic parameters selected by user. |
||
Ambient temperature and humidity |
From 0 to 55 °C, relative humidity from 5 to 95 % (without condensation). |
||
Storage temperature |
from -20 to 60° С |
||
Power supply |
Optional |
02 |
from 20 to 30 V DC, 20 W |
03 |
from 85 to 264 V AC, from 47.5 to 65.0 Hz, 20 W. |
||
Relay |
With break-make contact (C type), single-pole double-throw (SPDT), impeded into epoxied resin. |
||
Power backup (real-time clock) |
24 hour |
||
Inputs |
One or two galvanically isolated inputs for sensors. |
||
Outputs |
Four galvanically isolated current outputs 4-20 mA or 0-20 mA with active supply. Extensibility Maximum load: 550 Ohm |
||
Accuracy of current output |
± 0.05 mA at 25 °C |
||
Alarm</cf> |
Four signal relays for measurable process parameters and temperature. |
||
Camp connection specifications |
Socket: 24-12 AWG wires. Connector blocks on signal board: 26-16 AWG wires. Power sockets connectors: 26-16 AWG wires. Connector blocks of signaling relay: 24-12 AWG wires. |
||
Weight/shipping weight |
(rounded to 0.5 kg): 1.5 /2.0 kg |
||
Dimension |
157 x 157 x 132 mm |